SUN Wei, LI Yong, GUO Ruiyan, et al. Lightning Protection Characteristics of Surge Protective Gap Under Low Gas Pressure[J]. High voltageapparatus, 2014, 50(1): 26-30.
SUN Wei, LI Yong, GUO Ruiyan, et al. Lightning Protection Characteristics of Surge Protective Gap Under Low Gas Pressure[J]. High voltageapparatus, 2014, 50(1): 26-30. DOI: 10.13296/j.1001-1609.hva.2014.01.004.
Lightning Protection Characteristics of Surge Protective Gap Under Low Gas Pressure
A surge protective gap(SPG)is experimentally studied under low gas pressure ranging from 1 Pa to 2 000 Pa in terms of the characteristics of DC and impulse voltage breakdown
the voltage protection level
and the response time. The SPG is made of W-Cu materials with circular plate electrodes of 10 mm in diameter and 3 mm in gap.Experimental results indicate that a minimum appears in the DC breakdown voltage and the impulse breakdown voltage
the voltage ratio of UP to UC on the gap is from 2.10 to 2.94 under deferent gas pressure
and the response time increases gradually with gas pressure increasing.