SHI Huixuan, QIAN Jin, XIONG Zhidong, et al. Investigation on On-line Monitoring of SF6 Decomposition in Electrical Device[J]. High voltageapparatus, 2014, 50(1): 56-60.
SHI Huixuan, QIAN Jin, XIONG Zhidong, et al. Investigation on On-line Monitoring of SF6 Decomposition in Electrical Device[J]. High voltageapparatus, 2014, 50(1): 56-60. DOI: 10.13296/j.1001-1609.hva.2014.01.010.
Investigation on On-line Monitoring of SF6 Decomposition in Electrical Device
the detection of SF6decomposition in electrical equipments is off line. It is difficult to find the potential internal faults in the equipment as soon as possible. Based on the analysis of SF6decomposing characteristics
this paper presents an on-line monitoring system for decomposition by detecting SO2. The key technologies adopted in the system is detailed. According to researches
the electrochemical sensor is employed in the on-line monitoring system of SF6electrical device in the first time. Furthermore
the sample device based on flowing gas is proposed
which is quite important to ensure the accuracy for detecting SO2. Besides
the generation rate of the decomposition is calculated
and the system takes advantage of multi-level programmable gain method
which can enhance the ability for identifying weak signals and improve the accuracy and resolution of monitoring system. Finally the sensor calibration experiment and system test have been put into service on one SF6CT and one SF6circuit breaker in Zunyi substation