Experimental Study on Air-gap Discharge Characteristics in Heavy Humidity
Discharge characteristics of external insulation of power system are significantly influenced by atmospheric humidity. However
the existing researches seldom concern high humidity condition. In this study
air gap discharge tests were carried out in artificial climate chamber to investigate the relation between humidity(especially high humidity) and discharge voltage. The results show that:1)the discharge voltage increases with increasing humidity when relative humidity is less than 80%; 2)when relative humidity is above 80% the discharge voltage decreases slightly with the increase of humidity in the condition without dew
while it reduces to half of normal value in the condition with dew. The electric field in the air gap was calculated by the software ANSYS
and the result indicates that dew seriously distorts the electric field
making the maximum field strength doubled and resulting in a severe reduction in discharge voltage
which is consistent with the conclusions drawn from discharge tests in the artificial climate chamber.