OU Lin, WANG Yuhong, LI Xingyuan, et al. Analysis of AC-DC System Harmonic Distortion When the Power Substation and the Converter Station are Built Together[J]. High voltageapparatus, 2014, 50(3): 24-28.
OU Lin, WANG Yuhong, LI Xingyuan, et al. Analysis of AC-DC System Harmonic Distortion When the Power Substation and the Converter Station are Built Together[J]. High voltageapparatus, 2014, 50(3): 24-28. DOI: 10.13296/j.1001-1609.hva.2014.03.006.
Analysis of AC-DC System Harmonic Distortion When the Power Substation and the Converter Station are Built Together
The detail system model of Baoji-side AC system and Debao HVDC is built in PSCAD/EMTDC based on the real HVDC Transmission Project. The overall harmonic distortion rate and the individual harmonic ratio of various harmonics in AC system are calculated in the condition that the main transformer and converter transformer DC magnetic bias. The change trend of the harmonic distortion rate along with the increase of electrical distance coefficient K is analyzed. The power factor of rectifier side AC bus is calculated. The results show that the power factor is slightly increases with the increase of electrical distance coefficient K. At the same time
harmonic content and its change trend of DC voltage and DC current are analyzed. The power fluctuation value of the unipolar transmission power in DC system is calculated based on the harmonic content and its change trend of DC voltage and DC current
in which the third harmonic power fluctuation value is the largest and its impact on DC transmission power is the most obvious.