Combined Diagnosis of Partial Discharge for GIS Cable Terminal
Taking a typical partial discharge(PD)fault at a GIS cable terminal for example
the high frequency and ultra-high frequency PD detection methods as well as other approaches are adopted to preliminarily position the partial discharge source
then the source is accurately positioned by reading the pulse delay on a high-speed acquisition oscillograph. This positioning method is verified by experiment. Subsequently
the air-gap defect in the GIS cable terminal is detected accurately via CT scanning.