ZHEN Haohan, GUO Jie, LI Jiangtao, et al. Impact of Phase-shift Parameters on Overvoltage Caused by Ground Fault in Convertor Station of UHVDC[J]. High voltageapparatus, 2014, 50(5): 42-45+50.
ZHEN Haohan, GUO Jie, LI Jiangtao, et al. Impact of Phase-shift Parameters on Overvoltage Caused by Ground Fault in Convertor Station of UHVDC[J]. High voltageapparatus, 2014, 50(5): 42-45+50. DOI: 10.13296/j.1001-1609.hva.2014.05.009.
Impact of Phase-shift Parameters on Overvoltage Caused by Ground Fault in Convertor Station of UHVDC
S-blocking strategy is used to treat ground fault in convertor station of UHVDC. As the first step of the Sblocking strategy
phase-shift has a significant impact on the overvoltage caused by ground fault in the convertor station. In order to investigate the impact of phase-shift parameters on the ground fault induced overvoltage
the Xiangjiaba-Shanghai ±800 kV DC Power Transmission Project is taken as an example to analyze the overvoltage characteristics in the conditions of different phase-shift startup delay
speed and mode. The results show that the improved phase-shift startup delay has a more significant influence on the overvoltage caused by ground fault
and the existing phase-shift speed and mode for the project are suitable.