SHUAI Yong, HU Feng, ZHU Tifeng. Analysis on Overheat of Conductive Circuit of Transformer Equipment in Changde Power Grid with Countermeasures[J]. High voltageapparatus, 2014, 50(5): 120-125.
SHUAI Yong, HU Feng, ZHU Tifeng. Analysis on Overheat of Conductive Circuit of Transformer Equipment in Changde Power Grid with Countermeasures[J]. High voltageapparatus, 2014, 50(5): 120-125. DOI: 10.13296/j.1001-1609.hva.2014.05.023.
Analysis on Overheat of Conductive Circuit of Transformer Equipment in Changde Power Grid with Countermeasures
The overheat faults of the transformer equipment conductive circuit in Changde Power Grid are analyzed comprehensively to understand the distribution and features of the faults. According to the classical contact resistance theory in the electrical contact theory
the cause of the overheat equipment is analyzed by considering the terminal design
the bus-bar
and the installation specification of the transformer equipment. On the basis of the experience about operation and maintenance as well as the corresponding specifications
some precautionary measures are offered to the management of substation equipment maintenance and repair
such as replacing the screw contact by screw-hoop type wiring board
adopting composite copper/aluminum transition piece for the copper and aluminum butt contact
replacing the static contact ring of the screw-fastened joint by hoop-type contact
conducting loop resistance test in routine condition-based maintenance
performing on-site electric plating of finger(head)silver layer
and using a torque wrench for tightening acceptance.