Comparative Study on Corona Discharge Detection with Two Ultraviolet Imagers
Based on calculating the area of ultraviolet image discharge
the UV image quantitative research for rod-plate air gaps discharge was carried on by using the type of CoroCAM504 and OFIL series ultraviolet(UV) imagers respectively. The purpose of this study was to carry out comparative analysis to the difference about detecting corona discharge between the two main UV imagers at the moment. The study shows that: 1At the same condition of object distance
the image definition and field angle of two UV imagers are different; In contrast
the OFIL series is more suitable for shooting in details; 2At the same condition
the discharge facular areas of two UV imagers both increase
with the increase of the gain. The gain and discharge facular area approximately satisfies exponential function; 3At the same condition
the discharge facular area of two UV imagers both decrease when increasing the distance. The distance and discharge facular area is approximately exponential; 4Under the same test conditions and the same voltage level
the discharge facular area of OFIL series ultraviolet image detecting instrument is about 0.5 times of CoroCAM504’s
and the gain value of OFIL’s is about 2 times of CoroCAM504’s.