Study on AC/DC PLC Noise Filter for Nuozhadu ±800 kV DC Transmission Project
According to the limit value of PLC interference level in the tender invitation documents of Nuozhadu ±800 kV DC transmission project
noise filter configuration schemes are proposed
in which two reactors of 1.5 mH with tuner and a capacitor of 100 nF without tuner are equipped at AC side
and no PLC filter is needed on pole bus and neutral bus at DC side. The performance and rating of PLC filter are calculated. This study may provide a reference for the design of PLC filter in UHV and EHV DC transmission project.