XUAN Yaowei, ZHENG Xinlong, CHENG Binjie, et al. Calculation of Transient Overvoltage in AC Submarine Cable System[J]. High voltageapparatus, 2014, 50(9): 58-65.
XUAN Yaowei, ZHENG Xinlong, CHENG Binjie, et al. Calculation of Transient Overvoltage in AC Submarine Cable System[J]. High voltageapparatus, 2014, 50(9): 58-65. DOI: 10.13296/j.1001-1609.hva.2014.09.001.
Calculation of Transient Overvoltage in AC Submarine Cable System
To analyze the transient overvoltage caused by single-phase short circuit or three-phase short circuit in AC submarine cable system
simulation models were built on the platform PSCAD/EMTDC. For the neutral point grounded AC submarine cable system rated at 110 kV and the neutral point isolated AC submarine cable system rated at 35 kV
the overvoltage was calculated in the conditions of different transmission power
transmission distance
and short circuit capacity
and the relationship between the maximum overvoltage and these variables was analyzed. Moreover
the physical mechanism was discussed. This study may provide a reference for determining system parameters and insulation levels of submarine cable lines and substations.