ZHANG Qimin, ZHANG Liangxian, CHEN Mosheng. Calculation and Analysis of DC Electric Field in Valve-side Outlet Device of UHV Converter Transformer[J]. High voltageapparatus, 2014, 50(9): 66-70+75.
ZHANG Qimin, ZHANG Liangxian, CHEN Mosheng. Calculation and Analysis of DC Electric Field in Valve-side Outlet Device of UHV Converter Transformer[J]. High voltageapparatus, 2014, 50(9): 66-70+75. DOI: 10.13296/j.1001-1609.hva.2014.09.012.
Calculation and Analysis of DC Electric Field in Valve-side Outlet Device of UHV Converter Transformer
The valve-side outlet device is one of the most complicated and important insulation structures in a converter transformer. It withstands both AC voltage and DC voltage during operation stage. The electric field distribution in the device depends on the resistivity of insulation material under DC steady voltage. The resistivity of oil and pressboard is affected by electric field strength
showing nonlinear phenomena. The resistivity along and vertical to the layer of pressboard is quite different
showing anisotropic phenomenon. In this paper
the nonlinear and anisotropic DC electric field distribution in the valve-side outlet device is calculated and compared with the results of linear isotropic model and linear anisotropic model. Comparison reveals that both anisotropic and nonlinear characteristics should be taken into account in analysis and verification of DC electric field in the valveside outlet device.