Analysis on HVDC Voltage Abnormal Fluctuation of Tuanlin Converter Station
Tuanlin ±500 kV converter station DC line du/dt undervoltage protection reacted for two times. Oscillograph trace analysis
RTDS simulation
and theoretical calculation were conducted to determine that no fault happened in the DC line
and the reactions were caused by abnormal fluctuation of the measured voltage of Tuanlin converter station HVDC bus voltage divider. This paper introduces the abnormal fluctuation process of Tuanlin converter station HVDC voltage and the reason in detail. In this study
ground fault point inspection was performed for the DC voltage divider secondary measurement circuit
as a result
the abnormal fluctuation fault of high DC voltage could be removed
and the hidden shutdown risk of the DC system could be eliminated.