[1]郭飞,孔旭,吴旭涛,郭俊,刘青,AINIZIO A F,谢彦召.330kV超高压GIS开关动作VFTO辐射电场的测量与分析[J].高压电器,2014,50(09):119-125.
GUO Fei, KONG Xu, WU Xutao, et al. Measurement and Analysis of the Radiated Electric Field Excited by Switching Operation of 330 kV GIS[J]. High voltageapparatus, 2014, 50(9): 119-125.
GUO Fei, KONG Xu, WU Xutao, et al. Measurement and Analysis of the Radiated Electric Field Excited by Switching Operation of 330 kV GIS[J]. High voltageapparatus, 2014, 50(9): 119-125. DOI: 10.13296/j.1001-1609.hva.2014.09.021.
Measurement and Analysis of the Radiated Electric Field Excited by Switching Operation of 330 kV GIS
excited by very fast transient overvoltage(VFTO)during the operation of the breakers and the disconnecting switches
was measured and analyzed. First
a measuring system for the radiation field excited by VFTO was developed
and calibration results show that this measuring system has the features of anti-interference and wide-band response. Second
the system was applied to measure the radiation field excited by VFTO in a 330 kV GIS
and the results indicate that there is a significant difference between the radiation fields due to the operations of breaker and disconnecting switch. Even for same switch
different operation causes different radiation field. Analysis reveals a close relation between the discharge position and the energy distribution of the discharge-induced frequency spectrum.