Electric Field Computation and Analysis of Fittings in Quadruple Valve Hall of ±500 kV HVDC Converter Station
When the numerical simulation of the whole model of valve hall being done
if the known potential applied in different ways
the electric field distribution on surface of fittings within valve hall is also different. So potential and electric field simulation under the typical phase sequence is much needed.According to the waveforms of potentials appeared on the equipment in the valve hall
the transient potential application method is presented to calculate the electric field
which can really simulate the application of the potentials in valve hall with various frequency components. Compared to double-pulsed valve
the connection configuration of fittings in quadruple valve is relative complicated
and the difficulty of electric field calculation is also relatively high. Taking the real model in Zhaotong ±500 kV HVDC convertor station as example
the finite element simulation model is built up
the maximum field strength on surface of fittings is obtained which provide a reference for corona control in valve hall.