Effects of 500 kV Bus Sectionalizing Reactor on Transient Recovery Voltage and Countermeasures
Bus sectionalizing reactor is used to limit the magnitude of fault current in 500 kV power system. The effects of the bus sectionalizing reactor on transient recovery voltage(TRV) while limiting short circuit current are investigated in this paper. Taking the 500 kV Bus Sectionalizing Reactor Project in Jingmen for example
the effects of the bus sectionalizing reactor on TRV are analyzed in detail by using EMTP-ATP. The results show that the gradient of TRV is higher than the specified value in the standard
and connecting a capacitor of more than 0.1 μF in parallel with the serial reactor can reduce the gradient of TRV.