Application of Pulse Voltage to Polarity Testing for Potential Transformer
Whether the secondary side wiring polarity of potential transformer(PT) is correct or not is related to the correct operation of protection devices
and affect the operation stability of the entire power system. To meet the requirements of the smart grid construction
it is very necessary to develop the intelligent secondary side wiring polarity testing device of potential transformer. The traditional method of sinusoidal AC voltage
needs to analyze the primary and secondary voltage phase when microprocessor sampling. What’s more
the clock synchronization issues also exist and microprocessor needs to process a large amount of data. In this paper
we bring forward a new method: according to the secondary induced voltage waveforms to detect the secondary side wiring by applying pulse voltage transformer primary side.