Study on the Breaking Characteristic of AC Filter Circuit Breaker in ±1100 kV UHVDC Rectifier Side
the first ±1 100 kV UHVDC project is being planned and designed in China. Its rectifier side is planned to be supplied by 750 kV AC system
and has filtering and reactive compensation device with large capacity. Due to the characteristics of HVDC transmission system
the rectifier AC 750 kV system should be preconfigured for large capacity filter
reactive power compensation device. The operational voltage of device is high
and its capacity is large
so
for AC 750 kV filter and reactive power compensation device
it is necessary to study on the CB power load during switching operation
and the effect of reactive group capacity on CB power load. This paper mainly studied the CB power load under different operating condition with the EMTDC/PSCAD. It calculated the breaking current and recovery voltage under different operating condition and researched the breaking characteristic of circuit breaker with different reactive compensation. The research results provide some references for the filter grouping and circuit breaker selection.