Experimental Study on Explosion Protection Performance of Insulator with Built-in Surge Arrester Unit for 10kV Distribution Line
which combines the functions of insulator and line arrester with series-gap
can provide support and insulation for fixed-line
and restrain lightning over-voltage and power-frequency continuous current arc. Explosion protection performance is an extremely important issue in its design
and experimental study is necessary. In this study
two kinds of representative insulators were selected to conduct experimental research on their explosion protection performances through short-circuit current tests. The internal short circuit discharge energy of both kinds of insulators was obtained under the actions of the electric power and the thermal stress of power-frequency continuous current arc. The results show that the explosion protection performance of the composite insulators with built-in surge arrester unit is better than that of the porcelain insulators with built-in surge arrester unit. Small current short circuit test verifies that the explosion protection performances of both kinds of insulators meet the application requirement. According to the actual operating conditions of the arresters in distribution system
the explosion protection performance assessment of the insulators can take the single-phase grounded short-circuit fault condition into account.