YANG Fang, ZHU Zhihao, YUAN Duanlei, et al. Design of 40.5kV SF6 Circuit Breaker for Switching Reactive Loads[J]. High voltageapparatus, 2014, 50(11): 103-108.
YANG Fang, ZHU Zhihao, YUAN Duanlei, et al. Design of 40.5kV SF6 Circuit Breaker for Switching Reactive Loads[J]. High voltageapparatus, 2014, 50(11): 103-108. DOI: 10.13296/j.1001-1609.hva.2014.11.018.
Design of 40.5kV SF6 Circuit Breaker for Switching Reactive Loads
the research status of circuit breakers for switching reactive loads was reviewed briefly.Then
a dedicated SF6 circuit breaker for switching capacitor banks and reactors was designed considering the characteristic of high overvoltage during switching reactive loads. In the design process
such methods as for increasing the opening speed of the circuit breaker and optimizing the electric and gas flow fields were adopted to improve the breaker’s performance. Subsequently
the electric and gas flow fields in the interrupter was simulated.Based on the simulation and theoretical analysis
the dielectric strength was calculated
indicating that this circuit breaker can satisfy the design requirement. In addition
in accordance with the requirements in the standard IEC62271-100:2003
the designed circuit breaker passed the type test of switching reactive loads with high parameters in the KEMA test station in the Netherlands