XU Kangtai, TU Youping, LI Tianfu, et al. Contamination Characteristics of Composite Insulators on 500 kV Ling-Shen Transmission Line[J]. High voltageapparatus, 2014, 50(12): 1-6+13.
XU Kangtai, TU Youping, LI Tianfu, et al. Contamination Characteristics of Composite Insulators on 500 kV Ling-Shen Transmission Line[J]. High voltageapparatus, 2014, 50(12): 1-6+13. DOI: 10.13296/j.1001-1609.hva.2014.12.001.
Contamination Characteristics of Composite Insulators on 500 kV Ling-Shen Transmission Line
Pollution severity on insulator surface is related to the pollution areas classified and the determination of the insulation level
which is one of the basic problems for external insulation.This paper selects 10 composite insulators on 500 k V Ling-Shen AC transmission line in Shenzhen and investigates the natural contamination characteristics of insulators.The results of variance analysis show that the amount of pollution in different areas are close
however the pollution distribution along the string is uneven.The ESDD is higher at both the end of insulator and the pollution of the upper surface is more serious than lower surface on the insulator itself.This paper presents the non-uniform characteristics of contamination distribution
which should be taken into consideration in artificial pollution test.