TANG Wei, ZHANG Jianhong, WANG Zhenliang, et al. Study on the Terminal Structure Design of Metal-coating for Epoxy Resin Casting Insulator[J]. High voltageapparatus, 2014, 50(12): 137-140+146.
TANG Wei, ZHANG Jianhong, WANG Zhenliang, et al. Study on the Terminal Structure Design of Metal-coating for Epoxy Resin Casting Insulator[J]. High voltageapparatus, 2014, 50(12): 137-140+146. DOI: 10.13296/j.1001-1609.hva.2014.12.025.
Study on the Terminal Structure Design of Metal-coating for Epoxy Resin Casting Insulator
Solid insulated switchgear has been paid more and more attention by switchgear manufacturers.But we found that during actual manufacturing and testing process of epoxy resin casting insulator
the original electric field distribution of insulator is changed greatly due to metal-coating on outer surface of casting insulator and then results in many problems about electrical performance
such as partial discharge like needle discharge resulting from metal-coating terminal on inlet or outlet bushing insulator
is a typical and popular phenomenon.According to previous rich manufacturing and testing experience about solid in-sulated switchgear
combined with 3-D FEM simulation analysis
there have been solutions proposed
such as addition of shielding net without changing metal coating terminal location
addition of shed with changing metal-coating terminal location and addition of shed with groove and changing metal-coating terminal location.These proposed solutions proved by practical results are effective and feasible.
Research on Application of Microphone-optimized Spiral Arrays-based Acoustic Imaging Devices in Partial Discharge Localization
Study on Fiber Interferometric Partial Discharge Ultrasonic Sensing Method Based on Acoustic-optic Modulation and RF Phase Detection
High-frequency Sensing Technology of Partial Discharge of Switchgear Cabinet for Wind Solar & Energy Storage Stations in Gobi Deserts
Research on Influence of Piezoelectric Material Properties and Element Size on Sensitivity of Piezoelectric Sensor for Partial Discharge Monitoring of Transformer
Influence of Environmental Factors on Insulation Performance of Separable Connector for 12 kV Gas Filling Switchgear Cabinet
Related Author
YUE Song
GAO Fei
HAN Shuai
DONG Haoyuan
LI Jun
LI Xin
LIU Chao
QIAO Hui
Related Institution
Electric Power Research Institute of State Grid Tibet Company
China Electric Power Research Institute Co., Ltd.
Iflytek Co., Ltd.
Electric Power Research Institute, State Grid Hebei Electric Power Co., Ltd.
State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University