DONG Manling, DING Guojun, DONG Lijie, et al. Research on Circuit-breaker Lightning Failure of Open-ring Point in 220 kV Electromagnetic Loop Network[J]. High voltageapparatus, 2015, 51(1): 56-60+66.
DONG Manling, DING Guojun, DONG Lijie, et al. Research on Circuit-breaker Lightning Failure of Open-ring Point in 220 kV Electromagnetic Loop Network[J]. High voltageapparatus, 2015, 51(1): 56-60+66. DOI: 10.13296/j.1001-1609.hva.2015.01.010.
Research on Circuit-breaker Lightning Failure of Open-ring Point in 220 kV Electromagnetic Loop Network
A typical circuit-breaker lightning fault of open-ring point in 220 k V electromagnetic loop network is analyzed.The lightning intruding into the fracture of circuit-breaker occurs total internal reflection.And it’s the main reason causing the damage of circuit-breakers in recent years.Through the analysis
the installation of MOA
in the overhead line entrance of open-ring point in vulnerable area
is the most effective and safe method for prevention of circuit breaker from damage events.