Calculation of Very Fast Transient Overvoltage with the Arc Resistance Model Considering Inductance Characteristic
Taking a foreign 1 000 k V gas transformer substation(GTS)as example
the very fast transient overvoltage(VFTO)in the GTS is calculated by using the arc resistance model considering arc inductance characteristic
and the extreme of VFTO at key equipment in the GTS is analyzed.Results show that the arc resistance model can correctly simulate the physical process of arc in the isolating switch for analyzing the VFTO.Moreover
the effects of the intake capacitance
the static inductance
and the GIS branch length on VFTO are investigated.