WEN Yi, LI Chun, LI Jianming. Improved Model of Impulse Corona on Ultra High Voltage Alternating Current Transmission Lines[J]. High voltageapparatus, 2015, 51(2): 63-72.
WEN Yi, LI Chun, LI Jianming. Improved Model of Impulse Corona on Ultra High Voltage Alternating Current Transmission Lines[J]. High voltageapparatus, 2015, 51(2): 63-72. DOI: 10.13296/j.1001-1609.hva.2015.02.010.
Improved Model of Impulse Corona on Ultra High Voltage Alternating Current Transmission Lines
In the lightning insulation margin design of substation equipment
the attenuation and distortion of inbreaking lightning wave induced by impulse corona on transmission lines are ignored
leading to an over-strict requirement for the insulation margin. And the impulse corona exerts a significant influence on the withstand level calculation of lightning shielding failure. Therefore
it is necessary to investigate the impulse corona effect on UHV transmission lines. In this paper
a multi-conductor impulse corona model is proposed by considering the corona effect of overhead ground wire
the coupling between the transmission lines with corona
and the distribution feature of the corona capacitance between transmission line and ground. This model is well in accordance with the actual impulse corona discharge. Moreover
a lightning shielding failure simulation circuit of UHVAC transmission lines with corona is constructed by using ATP-EMTP. Simulation results show that impulse corona influences the wave process on the line to attenuate and distort the amplitude and steepness of lightning wave
so as to raise the withstand level of lightning shielding failure.