Calculation and Analysis on Main Insulation Flashover Fault of Circuit Breaker Caused by Lightning Overvoltage
To clearly discribe the transient process of lightning fault in a circuit breaker
a transient mathematical flashover model of basin-type insulator is constructed with the programing language models in EMTP
in which frequency effect and skin effect of overhead line in high-frequency domain are considered.The transient characteristics of lightning are analyzed for basin-type insulator with and without flashover.Moreover
the transient characteristics considering impulse corona are analyzed
and compared with those without considering impulse corona. The results illustrate that: 1 the breakdown of the circuit breaker is mainly due to the amplitude of lightning overvoltage on basin-type insulator exceeding its withstand limit(1 050 kV); 2 the amplitude of back flash overvoltage is lower than that of the shielding failure overvoltage; and 3 when impulse corona is taken into account