WU Deguan, YU Zhongtian, ZHOU Yu, et al. On-site Valve-side Partial Discharge Test Method of the Converter Transformer in ±800 kV UHVDC Transmission Project[J]. High voltageapparatus, 2015, 51(2): 136-140+145.
To conduct partial discharge test of converter transformer with Y-Δ connection in the ±800 kV UHVDC transmission project
an on-site ACLD with partial discharge test was implemented by symmetrically applying testing voltage on valve-side winding. In this paper
the testing method and its principle
the calculation of the testing parameters
and the on-site test implementation are discussed in detail. And the anti-interference measures for the testing circuit are described. Test results verify the feasibility and effectiveness of the ACLD with partial discharge test for UHV converter transformers by symmetrically applying voltage on the valve-side winding.