Discussion on Application Schemes of UHVDC Converter Station Bypass Pair
it is necessary for converter stations to apply bypass pair and to close bypass switches according to different control strategies
which is utmost important for isolating faults and keeping normal operation of other valve groups. However
mistaken application of the bypass pair will result in harmful effect on the ESOF or BLOCK process. In this paper
two situations(with and without application of bypass pair during BLOCK process) are discussed
and the actual waveforms of the two situations are analyzed. The result indicates that it is favorable to safe operation of UHVDC system in BLOCK process without application of bypass pair.