Analysis on Abnormal Phenomenon of UV Detection in High Altitude Substation
The audible noise caused by corona discharge of 500 kV electrical apparatus in Seergu substation is higher than that in other 500 kV substations. UV detection technology is used to detect defects and faults of high voltage electric apparatus by monitoring corona discharge around the apparatus. In this paper
the application of UV detection in Seergu substation is introduced
and the simulation test and electric field calculation of arrester grading ring are elaborated. The result shows that the obviously high corona noise is mainly caused by the colored paint stripping from the grading ring due to high altitude
strong wind
and great day- night temperature difference.Furthermore