LIU Hongwen, WANG Ke, MA Yi, et al. Aging Rule and Breakdown Voltage Prediction for Insulation of Generator Stator Winding[J]. High voltageapparatus, 2015, 51(3): 105-110+116.
LIU Hongwen, WANG Ke, MA Yi, et al. Aging Rule and Breakdown Voltage Prediction for Insulation of Generator Stator Winding[J]. High voltageapparatus, 2015, 51(3): 105-110+116. DOI: 10.13296/j.1001-1609.hva.2015.03.018.
Aging Rule and Breakdown Voltage Prediction for Insulation of Generator Stator Winding
Breakdown voltage is a characteristic parameter for representing main insulation aging of generator stator bar
and is the direct factor affecting generator service life. In this study
a sample of epoxy mica sheet with rated voltage of 8.5 kV was designed to simulate the insulation system of the 8.5 kV generator stator bar.Accelerated thermal aging experiment at 220 ℃ was conducted to obtain the practical characteristic parameters by analyzing the change trend of the insulation sheet’s characteristic parameters and combining with the validity analysis of breakdown voltage and characteristic parameters. It is shown that the characteristic parameters
Qmax
△C
C
△tanδ
and tanδ can be used to effectively predict breakdown voltage by means of BP neural networks.