LIN Xin, WEN Miao, SHEN Wen, et al. Analysis on Insulation Property of Converter Transformer Bushing Under Complex Voltage[J]. High voltageapparatus, 2015, 51(4): 1-6.
LIN Xin, WEN Miao, SHEN Wen, et al. Analysis on Insulation Property of Converter Transformer Bushing Under Complex Voltage[J]. High voltageapparatus, 2015, 51(4): 1-6. DOI: 10.13296/j.1001-1609.hva.2015.04.001.
Analysis on Insulation Property of Converter Transformer Bushing Under Complex Voltage
A converter transformer bushing suffers complex voltage in a high voltage direct current(HVDC)system. To comprehensively evaluate its insulation property
a numerical model is built to calculate the electric field distributions under different kinds of voltage with finite element method. Results show that: 1)under AC voltage the electric field distribution in the bushing is capacitive with potential contours concentrating in epoxy resin; 2)under DC voltage the electric field distribution in the bushing is resistive with potential contours concentrating in SF6gas; 3)the DC static voltage makes free charges accumulating on the surfaces of solid media to lead to a dramatic change of electric field distribution when the polarity reversal occurs
and a transient peak value of electric intensity appears in respective epoxy resin and silicon rubber after the polarity reversal; and 4)the peak value of electric field reaches up to 22.32 times of the static value in the middle of the shield