RUAN Xueyun, LI Zhiyuan, SONG Jian. Application Research on Vibration Velocity Method in the Converter Transformer Sound Power Measurement[J]. High voltageapparatus, 2015, 51(4): 24-28.
RUAN Xueyun, LI Zhiyuan, SONG Jian. Application Research on Vibration Velocity Method in the Converter Transformer Sound Power Measurement[J]. High voltageapparatus, 2015, 51(4): 24-28. DOI: 10.13296/j.1001-1609.hva.2015.04.005.
Application Research on Vibration Velocity Method in the Converter Transformer Sound Power Measurement
The converter transformer is one of the main noise sources in converter station and substation
the sound power measurement accuracy of the transformer affects noise evaluation and noise control. By studying the relationship between the structure surface vibration and noise of the converter transformer under no-load condition
this paper obtains the converter transformer acoustic radiation exponential curve according to the noise radiation exponent curve. Then through the field measurement of the surface vibration velocity of the same type converter transformer
the sound power level of the converter transformer can be calculated under the load. Compared with the method of sound intensity measurement
the results show that the vibration velocity measurement error of the converter transformer sound power level within 2 d B
which proves vibration velocity method applied in the field of converter transformer noise measurement is feasible. Compared with other methods sound power measurement
the method has a certain application prospect under the background of the current field test.