Simulation of PD Propagation Characteristics in XLPE Cables Based on Vector Fitting Model
Cross linked polyethylene cable are using more and more in distribution network due to its obvious advantages over other transmission equipment. Partial discharge(PD) detection and location is of great significance for the power cable insulation condition monitoring
where analysis of the PD propagation is needed. Considering the influence of skin effect and semi-conducting screens
this paper presents the single-core model of cross-linked polyethylene(XLPE)cable. To analysis the propagation of PD pulse in time domain
the model firstly is rational approximated using vector fitting method. Based on the fitting results
the π section lumped parameters model is then proposed. Two examples of two XLPE cables with different permittivity approximating forms of semiconducting screens are presented. Calculation results show that there is a strong attenuation for high-frequency PD pulse amplitude in cable. The proposed model can be used to analyse the propagation characteristics of PD signals
which will be helpful for the PD detection and defects identification in power cable.