SU Ge, QIN Xiaoyu, LI Songlei, et al. Study on Ferroresonance Generated in 550 kV GIS[J]. High voltageapparatus, 2015, 51(4): 145-150. DOI: 10.13296/j.1001-1609.hva.2015.04.027.
The electromagnetic voltage transformer(VT) configured in 550 k V GIS can generate ferroresonance under some special operating conditions. Through analyzing the causes of ferroresonance
it is con-cluded that the series LC circuit constituted by shunt capacitance between GCB breaks
the bus to earth capacitance in GIS
and the nonlinear inductance of VT are the main factors to generate ferroresonance.The T-area of 3/2 connection or 4/3 connection is the most dangerous operating condition. Furthermore
through validating ferroresonance by using EMTP analytical method
it is concluded that additional saturable reactor can effectively restrain ferroresonance.