Analysis of an EHVDC Transmission Line Fault Leading to Blocking Converter in ±800 kV Puer-Qiaoxiang EHVDC System
A transmission line fault in its unipolar metallic return mode has happened
leading to blocking converter in ±800 k V Puer-Qiaoxiang UHVDC system. This paper analyzes the fault in detail
and points out that the breakdown arrester in the neutral bus is the reason that causes neutral bus differential protection and polar differential protection action. In addition
part of DC protection design is imperfect. The optimization measures for corresponding DC protection are given.Practice has proved that the proposed measures effectively improve the reliability of the HVDC system operation.