LIN Xin, LI Dan, XU Jianyuan. Analysis on Seismic Performance of 800 kV Gas Insulated Switchgear(GIS)[J]. High voltageapparatus, 2015, 51(5): 8-13. DOI: 10.13296/j.1001-1609.hva.2015.05.002.
Analysis on Seismic Performance of 800 kV Gas Insulated Switchgear(GIS)
Aiming at the seismic performance of the 800 kV gas insulated switchgear(GIS)
the modal analysis theory is adopted to analyze its dynamic characteristics. Hence the structural natural frequencies and the mode shapes are obtained. By using the theories of response spectrum and time history analysis
the vibration characteristics of the structure are analyzed. Through the response spectrum analysis and the dynamic time history analysis with Tianjin wave
EI-Centro wave
and Taft wave
the consistency and limitation of the results from both analysis methods are discussed. According to the effects of different seismic waves on the GIS equipment
conclusions are drawn that compared with taft wave
Tianjin wave with smaller amplitude and shorter duration imposes bigger destructive effect; and the EI- Centro2 wave with higher/lower frequency exerts bigger impact on the structure than the EI-Centro1 wave with same amplitude and lower/higher frequency.