TANG Mingjun, YE Lisha, LIN Chunyao, et al. Optimization of Shielding Ring of Insulator String in 500 kV Substation[J]. High voltageapparatus, 2015, 51(5): 63-70.
TANG Mingjun, YE Lisha, LIN Chunyao, et al. Optimization of Shielding Ring of Insulator String in 500 kV Substation[J]. High voltageapparatus, 2015, 51(5): 63-70. DOI: 10.13296/j.1001-1609.hva.2015.05.012.
Optimization of Shielding Ring of Insulator String in 500 kV Substation
均压环表面最大场强峰值可降至14.5 kV/cm;双联串均压环最佳结构参数为:屏蔽绝缘子片数3、管径100 mm、与绝缘子距离90 mm
均压环表面最大场强峰值可降至14.7 kV/cm。计算结果证明
优化后的均压环明显改善绝缘子串电压分布
降低了单片绝缘子承担的最大电压
并使均压环表面最大场强峰值低于20 kV/cm。
Abstract
To restrain the corona discharge phenomena in Gangcheng 500 kV substation
according to the actual circumstance of the substation
simulation models of suspension insulator string and double tension insulator string are established in ANSYS by using finite element method. The influences of different structural parameters of shielding rings on electric field and voltage distribution along an insulator string are calculated to achieve the optimum structural parameters of a shielding ring. Simulation results show that the optimum structural parameters of shielding ring are: 230 mm in cover depth
660 mm in diameter
and 70 mm in caliber for the 500 kV suspension insulator string
which can reduce the maximum peak value of electric field strength on the shielding ring to 14.5 kV/cm; and 3 in number of ring shields
100 mm in caliber
and 90 mm in distance between shielding ring and insulator for the double tension insulator string
which can reduce the maximum peak value of electric field strength on the shielding ring to 14.7 kV/cm. Calculation results show that the optimized shielding ring obviously improves the voltage distributions along the suspension insulator string and double tension insulator string
reduces the maximum voltage on single insulator
and makes the maximum peak value of electric field strength on shielding ring lower than 20 kV/cm.