Measurement and Analysis of Partial Discharge on Floating Electrode Defect in GIS
Partial discharge(PD)characteristics of floating electrode defect in gas insulated switchgear(GIS)sample were investigated. Physical model of floating electrode defect was designed and placed in the cavity in a220 kV GIS for experiment. The voltage on GIS was gradually increased to make in-depth observation of PD development process. The pulse current method
the UHF method and the ultrasonic method were used to monitor the PD process and obtain PD characteristics and development trend of the defect. Experimental results showed that the PD became more violent with the increase of applied voltage with larger discharge number
higher discharge amplitude
and wider phase interval. In addition
the time-domain spectrum
frequency-domain spectrum and PRPD spectrum of PD were obtained from the PD data of UHF signals to evaluate the severity of partial discharge generated by the floating electrode defect. Comparison among the three PD detection methods indicates that the UHF method is more suitable for online partial discharge detection because of its better anti-interference performance and higher sensitivity.