Analysis of Oscillating Over-voltage Breakdown Fault of 35 kV XLPE Power Cable with Countermeasures
several breakdown failures of XLPE power cable have happened in Beijing power grid
which have threatened the power grid security. In this paper
the cause of the oscillating over-voltage breakdown failure and the accident process are analyzed to further understand the impact of the oscillating over-voltage on electric power equipment. Taking the breakdown fault of 35 kV power cable of a transformer substation for example
the main-line diagrams of the grid and the fault description are given
disassembly inspection of the cable middle joint is conducted
and the fault recorder data are analyzed. Conclusion is drawn that the breakdown fault is caused by transient single-phase grounding due to the touch of crane and overhead wires
which activates low frequency oscillation of local 35 kV system to generate oscillating overvoltage. Moreover