YANG Lansuo, LI Min, WANG Xiaoqin, et al. Effects of Vacuum Switchgear Contact Structure on Magnetic Flux Density and Electromagnetic Force[J]. High voltageapparatus, 2015, 51(5): 193-198.
YANG Lansuo, LI Min, WANG Xiaoqin, et al. Effects of Vacuum Switchgear Contact Structure on Magnetic Flux Density and Electromagnetic Force[J]. High voltageapparatus, 2015, 51(5): 193-198. DOI: 10.13296/j.1001-1609.hva.2015.05.036.
Effects of Vacuum Switchgear Contact Structure on Magnetic Flux Density and Electromagnetic Force
得出了触头结构形式对磁感应强度和电磁力的影响规律。16匝横磁触头结构的最大磁感应强度值(49.21 m T)最小
4匝横磁触头结构的最大磁感应强度值(63.86 m T)居中
螺旋槽横磁触头结构的最大磁感应强度值(74.54 m T)最大。16匝横磁触头结构电弧模型的电磁力(0.042 1 N)最小
4匝横磁触头结构电弧模型的电磁力(0.063 6 N)居中
螺旋槽横磁触头结构电弧模型的电磁力(0.117 6 N)最大。
Abstract
The magnetic flux density and electromagnetic force of different structures of transverse magnetic field(TMF)contacts are analyzed by using simulation method
and the effects of the contact structure on magnetic flux density and electromagnetic force are obtained. The results show that: 1)the maximum value of magnetic flux density of the 16-turn TMF contact is 49.21 m T
the 4-turn TMF contact 63.86 m T
and the screw slotted TMF contact 74.54 m T;2)the arc model’s electromagnetic force of 16-turn TMF contact is 0.042 1 N