Accidents Analyses of Porcelain Post Insulators of 220 kV Tubular Busbar
To reveal fracture accidents of porcelain post insulators of a tubular busbar for safe
stable and reliable operation of a power system
five accidents of porcelain post insulators of a 220 kV tubular busbar are analyzed.Field investigations and experimental analyses are conducted to analyze the features of these accidents
and possible causes are discussed in detail with respect to porcelain quality
type selection
installation
operation
and maintenance. It is concluded that the major causes of the fracture accidents of the porcelain post insulators include poor quality of porcelain material
insufficient bending strength
wrong fixing mode of the tubular busbar
improper selection of busbar support type
and sustained heavy wind. Moreover
some corresponding countermeasures against the fracture accidents of the post porcelain insulators are given.