Influence of Smoothing Reactor Arrangement on Overvoltage of ±800 kV UHVDC Converter Station
通常±500 k V直流输电工程(HVDC)的平波电抗器采用油浸式电抗器安装在极母线上。因为±800 k V特高压直流输电的特殊性
平波电抗器采用了干式平抗
并提出了将4台干式平抗分别安装于极线和中性母线上的布置方式。文中对平抗分置于极线和中性母线上
与集中布置于极线上这两种布置方式下的换流站绝缘配合进行了分析
并对决定换流站各避雷器最大应力的工况进行了仿真计算
对计算结果进行了比较分析
并总结了这两种布置方式的优缺点。
Abstract
±500 k V HVDC system usually uses oil immersed smoothing reactors
which are installed on the pole bus. Considering the particularity of ±800 k V UHVDC system
the dry smoothing reactors are applied.Four dry smoothing reactors are arranged separately on the pole bus and the neutral bus to provide equal smoothing reactance for the converter station. In this article
this reactors arrangement scheme is compared with the scheme in which all the smoothing reactors are installed on DC pole bus to investigate the influences of both arrangement schemes on the insulation coordination of the converter station. Simulation is conducted to calculate the critical condition in which each arrester in the converter station can achieve its maximum stress. Comparative analysis is performed on the simulation results to reveal the advantages and disadvantages of two smoothing reactors arrangement schemes.