CAO Hongliang, YANG Zhongjiang, HUA Rongqiang, et al. Study on Algorithm of Resistive Current of MOA[J]. High voltageapparatus, 2015, 51(7): 32-36. DOI: 10.13296/j.1001-1609.hva.2015.07.006.
The fundamental harmonic resistive current ir1 and the third harmonic resistive current ir3 generated by the fandamental voltage can reflect the operation state of metal oxide arrester(MOA). The traditional MOA capacitive current compensation algorithm and its improved algorithm didn’t take the harmonic voltage into consideration
so it will produce errors in theory. In order to resolve the problem
and on the basis of traditional algorithm
the new equivalent resistance algorithm is proposed in this paper so that a part influence of harmonic voltage on the resistive current is eliminated and the precision of ir1 and ir3is improved. The results simulated by MATLAB show that the error of ir1 and ir3can be reduced. Especially that the ir3 is reduced by half
and the effectiveness of the modified algorithm is verified
Study on the Harmonic Resistive Current Compensation Algorithm of MOA
Digitizing Detection of Resistive Current of MOA Based on Harmonic Analysis Method
ON-LINE MEASURING RESISTIVE CURRENT OF MOA AND ITS ANGLE CORRECTION
Discuss on the Analysis Method of Resistive Current of MOA under Live Test
PROPOSAL TO ALARM CURRENT REFERENCE VALUE OF ZnO ARRESTER
Related Author
ZHANG Zhi-peng1
YANG Zhong-jiang1
杨芝田
陈志明
任凡
顾乐观
孙才新
王忠毅
Related Institution
Key Meteorological Disaster Laboratory of Ministry of Education Established Jointly by Provincial Department,Nanjing University of Information Science & Technology
School of Atmospheric Physics,Nanjing University of Information Science & Technology