JIANG Nan, LI Suichao. Testing Method for Capacitance Current of Insufficiently Grounded Power System to Ground[J]. High voltageapparatus, 2015, 51(7): 121-124.
JIANG Nan, LI Suichao. Testing Method for Capacitance Current of Insufficiently Grounded Power System to Ground[J]. High voltageapparatus, 2015, 51(7): 121-124. DOI: 10.13296/j.1001-1609.hva.2015.07.024.
Testing Method for Capacitance Current of Insufficiently Grounded Power System to Ground
5 kV insufficiently grounded power system to ground
a testing method was proposed
in which a capacitance current tester of distribution network is used for the test by means of the different-frequency method at open delta of a three-phase voltage transformer
and the difference of measured data of PT with load on line and without load is calculated to determine the capacitance current of the6
3
5 kV insufficiently grounded power system to ground. On-line test was conducted on 19 lines of the 6
3
5 kV distribution network in a power plant
the test data were analyzed to verify the correctness of the proposed testing method. Part of the lines were modified acco
rding to the data
and the result demonstrate the feasibility and accuracy of the proposed method.