Analysis of the Causes of Abnormal CO Content in On-site Test of SF6 Decomposition Products
How to strengthen the monitoring of SF6 decomposition products is very important for detection of abnormal timely in the electric power system at present. This paper analyzes several methods for detection of SF6 decomposition gases. Many times tests of CO content of 5042
5043 switch on-site is abnormal
and its SF6 gas of one 500 kV station is used to carry out in laboratory. The study found that the results of on-site test are different from dates of laboratory test. According to the analysis of experimental results and the principle of instruments a conclusion is drawn that the certain type testing instruments on-site have some defects of structural defects exist gas mutual interference. They cannot separate H2 and CO completely
leading to calculating the CO content as the amount of H2 mistakenly. Inaccurate data is a great disturbance to accurately determine the equipment faults. To solve this problem
this paper puts forward suggestions for on-site detection.