XIAO Gan. Comparison Between Two Design Schemes of Converter Transformer’s Barrier System[J]. High voltageapparatus, 2015, 51(7): 195-199. DOI: 10.13296/j.1001-1609.hva.2015.07.037.
Comparison Between Two Design Schemes of Converter Transformer’s Barrier System
Two barrier systems of converter transformer were designed with same thickness of insulation pressboard cylinder and different oil gap. To compare their insulating strength
the software Elec Net is adopted to calculate the electric field intensities and withstand voltages of two designed barrier systems. The results show that the electric field intensity of the barrier system with smaller oil gap is lower than that of the other barrier system
suggesting that the barrier system with smaller oil gap is more applicable.