SUN Lipeng, LI Zhiyuan, JIANG Zhenglong, et al. Calculation and Selection of the Key Parameters of Power Supply for UHV AC Artificial Contamination Test[J]. High voltageapparatus, 2015, 51(8): 16-23.
SUN Lipeng, LI Zhiyuan, JIANG Zhenglong, et al. Calculation and Selection of the Key Parameters of Power Supply for UHV AC Artificial Contamination Test[J]. High voltageapparatus, 2015, 51(8): 16-23. DOI: 10.13296/j.1001-1609.hva.2015.08.003.
Calculation and Selection of the Key Parameters of Power Supply for UHV AC Artificial Contamination Test
The power supply for ultra-high voltage(UHV)AC contamination test is a main equipment in artificial contamination and icing tests at AC UHV level or below
so the test reliability depends on the selection of its parameters. The authors put forward a method for calculating key parameters of the power supply
and analyze the influences of the key parameters on the artificial contamination test at AC UHV level or below. Calculation results show that: for different test voltage level
protective resistor with corresponding resistance should be selected in order to obtain satisfactory results of the AC contamination test; the withstand short circuit capacity of the transformer should be at least 9 times of its rated current for UHV AC contamination test
and at least 6 times for EHV or lower voltage contamination test.