LI Dawei, XU Dangguo, SUN Yunsheng, et al. Mechanical Defect Diagnosis and Testing Method of High Voltage Circuit Breakers Based on Opening/Closing Coil Current Parameters[J]. High voltageapparatus, 2015, 51(8): 114-118.
LI Dawei, XU Dangguo, SUN Yunsheng, et al. Mechanical Defect Diagnosis and Testing Method of High Voltage Circuit Breakers Based on Opening/Closing Coil Current Parameters[J]. High voltageapparatus, 2015, 51(8): 114-118. DOI: 10.13296/j.1001-1609.hva.2015.08.019.
Mechanical Defect Diagnosis and Testing Method of High Voltage Circuit Breakers Based on Opening/Closing Coil Current Parameters
The opening/closing coil is a key component of high voltage circuit breaker’s operating mechanism. The authors analyze the relationship between the current waveform of breaker opening/closing coil and the mechanical defects
extract the key characteristics of the coil current waveform
and hence establish a diagnosis criterion for typical mechanical defects of circuit breaker. This diagnosis method is verified on a simulation test platform in laboratory. Further
the coil current test method of circuit breaker for"first opening/closing operation"is put forward.