YANG Shufeng, CHEN Hui. Dielectric Loss Measurement Method of Parallel Capacitor Between GIS Circuit Breaker Contacts in Xiluodu Hydropower Station[J]. High voltageapparatus, 2015, 51(8): 136-140.
YANG Shufeng, CHEN Hui. Dielectric Loss Measurement Method of Parallel Capacitor Between GIS Circuit Breaker Contacts in Xiluodu Hydropower Station[J]. High voltageapparatus, 2015, 51(8): 136-140. DOI: 10.13296/j.1001-1609.hva.2015.08.023.
Dielectric Loss Measurement Method of Parallel Capacitor Between GIS Circuit Breaker Contacts in Xiluodu Hydropower Station
the whole dielectric loss of the parallel capacitor between the circuit breaker contacts cannot be measured because its adjacent circuit breakers at both sides or the busbar still operate with electricity. In this paper
the difficulties in measurement of whole dielectric loss of parallel capacitor between contacts of a GIS circuit breaker in outage state are analyzed. A method of "connecting before break"to prevent high voltage and ensure safety and "forming neutral point"to eliminate coupling high voltage and strong electric field interference is proposed. Test results verify that this method is safe