QIU Zhibin, RUAN Jiangjun, HUANG Daochun, et al. Mechanical Faults Analysis of High Voltage Disconnectors and Review of Diagnosis Technology[J]. High voltageapparatus, 2015, 51(8): 171-179.
QIU Zhibin, RUAN Jiangjun, HUANG Daochun, et al. Mechanical Faults Analysis of High Voltage Disconnectors and Review of Diagnosis Technology[J]. High voltageapparatus, 2015, 51(8): 171-179. DOI: 10.13296/j.1001-1609.hva.2015.08.029.
Mechanical Faults Analysis of High Voltage Disconnectors and Review of Diagnosis Technology
Frequent faults of high voltage(HV)disconnectors seriously threaten the safety and stability of power grid. Mechanical faults are the most common failure type of outdoor disconnectors. In this study
the causes of the typical mechanical faults of a disconnector
including rupture of porcelain post insulator
malfunction and corrosion
were analyzed. And the present researches on mechanical fault diagnostic methods of HV disconnectors
such as ultrasonic flaw detection
acoustic vibration technique
infrared thermography
stress-strain measurement
and driving motor current signal detection
were reviewed. Furthermore
sticking faults of transmission or rotating mechanism of a disconnector were detected by resistance strain gauge and motor current signal analysis
and the results were preliminarily analyzed. On this basis
several suggestions about comprehensive mechanical fault diagnosis of HV disconnector were offered to provide reference for installation
debugging
operation and maintenance of HV disconnectors in outdoor substations.