YANG Jinggang, JIA Yongyong, ZHAO Ke, et al. Analysis of an Excessive Resistance Phenomenon of 550 kV Circuit Breaker Closing Resistor[J]. High voltageapparatus, 2015, 51(8): 197-199+204.
YANG Jinggang, JIA Yongyong, ZHAO Ke, et al. Analysis of an Excessive Resistance Phenomenon of 550 kV Circuit Breaker Closing Resistor[J]. High voltageapparatus, 2015, 51(8): 197-199+204. DOI: 10.13296/j.1001-1609.hva.2015.08.033.
Analysis of an Excessive Resistance Phenomenon of 550 kV Circuit Breaker Closing Resistor
The resistance of a 550 k V circuit breaker closing resistor was found exceeding the standard value in a routine test. Then disassembly inspection and test were conducted. It was discovered that this type of closing resistor possesses a negative temperature characteristic
and its resistance increases when the ambient temperature decreases. In order to ensure accurate on-site measurement of the closing resistor
it is suggested that the influence of ambient temperature should be considered in production of this type of closing resistors
and ambient temperature ought to be recorded for resistance conversion in process of measurement.